Question:
I have 200 amp Panel The neutral and ground wire for each circuit are together on the ground bar is this ok by code
DEAN CARNES
A
Answer:
Hey Dean thanks for your question. If by together you mean in the same terminal (hole) then no. Each grounded conductor must terminate in an individual terminal that is not also used for another conductor as stated in 408.41.