Wednesday, September 25, 2019

Question:

Re: CQD answer published Thursday, September 12, 2019 - Fence Grounding

1) In reference to fence grounding at industrial facilities; if there are transmission lines nearby, running parallel to a long fence or pipe line, they can induce current into the fence or other metal structures. This current will seek a ground path in order to return to it's source. I have witnessed arcing between a non-grounded fence where it "almost" touches a grounded fence section. Daniel Cribbs

2)I  am not sure about his facility and the reasons, but there are several reasons for the grounding of the fences. My guess from his description is that it is probably for Lightning protection.

A) Lightning arresting – Lightning can travel great distances in a metal fence if it is not grounded well. This could easily cause damage to people, structures or objects thousands of feet away from the strike.

B) Posts that only go down two feet may be in earth that has too high of resistance to effectively ground against lightning. In few soils will two feet be enough for proper grounding. Earth resistance measurements will be required to specify the Grounding rod length. “Rule of thumb” in this case may be due to previous ground resistance measurements, but may not hold true for earth 1000’ away. It is not a safe bet that adding grounding rods every 50’ would provide the proper protection unless tested. Grounding testing should be done on a regular basis to maintain the integrity of the protection, typically once a year for building protection, but maybe less often for fencing as long as there is a regular visual inspection for loose connections, mower damage, etc.

C) Metal fences around Medium and high voltage substations also require Grounding to prevent static and stray voltages from energizing the fence and have much greater Grounding requirements than that for lightning protection.

Thank you, Ratib Baker, CMS, RCT
A

Answer:

ABOUT CQD: The Code Question of the Day (CQD) is NECA and ELECTRICAL CONTRACTOR Magazine’s flagship National Electrical Code (NEC®) public forum for the industry, sponsored by EATON. The daily distribution of Q&A generates a lively dialogue and shares relative Code-based practical responses.

SUBMIT YOUR CODE QUESTION: Click here to submit a question to for inclusion in an upcoming edition of the Code Question of the Day, or email codequestion@necanet.org

CHARLIE TROUT: Charles M. Trout, better known as Charlie, was a nationally known NEC® expert and author. He served on several NEC® technical committees and is past chairman of CMP-12. In 2006 Charlie was awarded the prestigious Coggeshall Award for outstanding contributions to the electrical contracting industry, codes and standards development, and technical training. Even though Charlie passed away in October of 2015, his work continues in spirit. NECA continues to maintain this question forum for its many subscribers in memory and recognition of all his significant contributions to making the NEC what it is today.

NECA STANDARDS: NECA publishes the National Electrical Installation Standards™ (NEIS™), a series of ANSI-approved performance and quality standards for electrical construction. NEIS can be purchased in the NECA Store in three formats: a printed or  PDF download of a standard or, as an  annual subscription service.

NECA SAFETY PRODUCTS & PUBLICATIONS: NECA produces electrical safety publications and products for the industry including jobsite safety guides, handbooks and resource kits. View a full listing of available resources and products »

IMPORTANT NOTICE: Unless the question requests a response based on a specific edition, all answers are based on the latest edition of NFPA 70® National Electrical Code®.

This correspondence is not a formal interpretation of the NEC® and any responses expressed to the questions are opinions and do not necessarily represent the official position of NECA, NFPA, the NEC Correlating Committee any Code-making panel or other electrical technical committee. In addition, this correspondence is neither intended, nor should it be relied upon, to provide professional consultation or services. 

UPDATE YOUR SUBSCRIPTION PREFERENCES: Subscribe or Unsubscribe from this list.