Wednesday, September 1, 2021
Question:
Hello CQD,
What distance and code references are required for separation between 120 VAC and up and say Category 6 cable for data.
Larry Walker
A
Answer:
Hi Larry,
The type of system in the Category 6 cable is not mentioned in the question, but since it is data, we will use Article 830 for the response. Section 830.133(A) provides the general separation requirements for network-powered broadband communications cables and power and lighting circuit conductors. 830.133(A)(2) indicates a separation of at lease 2 inches is required from any electric light, power, Class 1 and nonpower limited fire alarm circuits.