Tuesday, March 8, 2022
Question:
Hello CQD,
What is the minimum working space required for a control panel of a 480-volt electric heater? The control panel contains a contactor, control transformer, disconnecting means, and fuses. There are other electronics in this panel too.
Thanks for any info you can provide.
Carl Minor
A
Answer:
Hello Carl,
Thanks for participating. The minimum depth of working space required in front of the heater control panel is 36 inches based on Section 110.26(A) and Table 110.26(A)(1).