Question:
Hello,
We just purchased a home and the receptacle for the refrigerator is on a 20-ampere separate circuit. Does it require GFCI protection in accordance with the NEC? This outlet and branch circuit only supplies the refrigerator in the kitchen.
Thanks for your time.
Paula Adams
A
Answer:
Hi Paula,
Based on the information in the question, the GFCI protection is not required. See Section 210.8(A)(6) which indicates that receptacles installed to serve countertop surfaces require GFCI protection.