Question:
Do the controls for a septic pumping station need to be with in the sight of the pump station.
Sean McCarthy
A
Answer:
Hey Sean thanks for your question. The NEC does not require that control devices be in sight of the equipment they operate but doing that seems like a good idea. Disconnecting means for controllers and motors must be within sight under the conditions stated in 430.102.