Question:
Re: CQD answer published Thursday, November 8, 2018 - Service Entrance Cable
Folks, Do not forget SE and USE are not allowed to be installed in conduit underground.
Cordially,
Bill Nolte, C.S.H.O.
A
Answer:
Hey Bill thanks for your comment. You are correct about the SE cable not being allowed underground as we stated in the answer - except for temporary use as feeders and branch circuits as stated in 590.4(B) & (C). But USE can be installed in raceways underground because it is not prohibited in 338.12 and allowed by the respective raceway article in the .22 section.