Question:

Per 2017 NEC, is shared neutral conductor permitted in multiwire branch circuits to serve line-to-neutral loads for lighting and/or receptacles installed indoor? Section 200.4(B) states that "unless specifically permitted elsewhere in this Code". Specific requirements in sections 215.4 and 225.7 permit multiple circuits to have a common or shared neutral conductor.

Jesus Santos
A

Answer:

Hey Jesus thanks for your question. Yes, and they are not limited to indoors. Multiwire branch circuits are allowed as stated in 210.4 under the conditions provided and can be considered as multiple circuits - even though they are not multiple circuits. The definition of Branch Circuit, Multiwire in Article 100 indicates it is "A" branch circuit and the ungrounded conductors have a voltage between them. As you mention the neutral conductor is "shared" between multiple ungrounded conductors from different phases (or lines) of a circuit. A multiwire circuit supplied from a three-phase system (A, B, C and Neutral conductor) has essentially the equivalent load capacity as three separate 2-wire branch circuits, but it is considered one circuit.

As you also mention, neutral conductors are not allowed for more than one branch circuit or one multiwire branch circuit or one set of ungrounded feeder conductors as stated in 200.4(A), unless specifically permitted elsewhere in this Code. For lighting equipment installed outdoors, a neutral conductor can be used for multiple circuits as stated in 225.7(B). In this arrangement there could be 2 A phase, 2 B phase, and 2 C phase 20 ampere ungrounded conductors with 1 (single) 40 ampere neutral conductor - used as a common neutral conductor. There are limits of how many sets of feeder conductors as stated in 215.4. Although the word "shared" is not used in the definition of Branch Circuit, Multiwire, in 210.4, 215.4, or 225.7 it is a good way of differentiating between common neutral conduct and those that are for a single branch circuit (2 wire or multiwire).

ABOUT CQD: The Code Question of the Day (CQD) is NECA and ELECTRICAL CONTRACTOR Magazine’s flagship National Electrical Code (NEC®) public forum for the industry, sponsored by EATON. The daily distribution of Q&A generates a lively dialogue and shares relative Code-based practical responses.

SUBMIT YOUR CODE QUESTION: Click here to submit a question to for inclusion in an upcoming edition of the Code Question of the Day, or email codequestion@necanet.org

CHARLIE TROUT: Charles M. Trout, better known as Charlie, was a nationally known NEC® expert and author. He served on several NEC® technical committees and is past chairman of CMP-12. In 2006 Charlie was awarded the prestigious Coggeshall Award for outstanding contributions to the electrical contracting industry, codes and standards development, and technical training. Even though Charlie passed away in October of 2015, his work continues in spirit. NECA continues to maintain this question forum for its many subscribers in memory and recognition of all his significant contributions to making the NEC what it is today.

NECA STANDARDS: NECA publishes the National Electrical Installation Standards™ (NEIS™), a series of ANSI-approved performance and quality standards for electrical construction. NEIS can be purchased in the NECA Store in three formats: a printed or  PDF download of a standard or, as an  annual subscription service.

NECA SAFETY PRODUCTS & PUBLICATIONS: NECA produces electrical safety publications and products for the industry including jobsite safety guides, handbooks and resource kits. View a full listing of available resources and products »

IMPORTANT NOTICE: Unless the question requests a response based on a specific edition, all answers are based on the latest edition of NFPA 70® National Electrical Code®.

This correspondence is not a formal interpretation of the NEC® and any responses expressed to the questions are opinions and do not necessarily represent the official position of NECA, NFPA, the NEC Correlating Committee any Code-making panel or other electrical technical committee. In addition, this correspondence is neither intended, nor should it be relied upon, to provide professional consultation or services. 

UPDATE YOUR SUBSCRIPTION PREFERENCES: Subscribe or Unsubscribe from this list.