Question:
Good Morning,
The question today is how many service's are permitted on a building? Is there an allowance to have a separate service for a fire pump?
Thanks for any guidance you can provide.
The Ardent Team
A
Answer:
Greetings Ardent Team,
Thanks for participating. Section 230.2 of the NEC generally limits each building to one service unless additional service(s) are permitted by 230.2(A) through (D). There are several allowances for more than one service. It's also a good idea to inquire with the local authority having jurisdiction for any other requirements beyond the NEC minimums.