Wednesday, March 18, 2020
Question:
Thanks for this forum. It provides useful information. I have a question pertaining to emergency generators installed for a commercial building. When the utility power fails, is there a maximum time that emergency generator power must be restored so people are not left stranded in the dark? I can't seem to find a rule that clarifies this. Thanks for you help on it.
Thomas Seneca
A
Answer:
Hi Thomas, thanks for the nice comments and participating in Code Question of the Day. This is a fairly simple question at face value, the answer is going to be short and simple too. The answer is yes, the NEC does specify a maximum time for emergency power/lighting transfer and it is 10 seconds. For an emergency system, this requirement is found in Section 700.12. Hope this is useful.