Question:
Our electrical room is 1200 amp service. The architect wants to depress the floor so this will have steps. Doesn't this have to been level service to exit?
Mike Conley
A
Answer:
Hey Mike thanks for your question. Steps are not prohibited for the electrical equipment space in 110.26 or by Article 230. Overcurrent devices are not allowed to be located above steps as stated in 240.24(F).