Question:
High Rise Hotel -Typical Electrical Room - Vertical Feeder Bus duct. We have (2) 2 section panels in the room. Both are fed from the vertical bus duct. This will require 2 bus plugs on the same bus duct. Is there a min / max mounting height requirement to mount these bus plugs.
Dale Daniels
A
Answer:
Hey Dale thanks for your question. No. Busway switches do not need to be readily accessible as stated in 404.8(A) Exception 1. There is no minimum mounting height.