Tuesday, July 25, 2017
Question:
Exemption for Agricultural Bldg. Bldg is to be used for hay storage and maintenance of farm equipment. Can I set a 200a panel with a meter? Wiring to method to be UF
Joel Hendren
A
Answer:
Hey Joel thanks for your question. Underground feeder and branch circuit cable can be used in agricultural buildings as stated in 547.5(A). It is not allowed to be used as service-entrance cable as stated in 340.12(1) or where subject to physical damage as stated in 340.12(10). The equipment must also be suitable, with no openings, as stated in 547.5(C)(1). Depending on what you mean by "farm equipment maintenance" other requirements could apply such as Article 511.