Question:
Good morning & thanks for your work. I have seen a lot of non metallic flex (Carflex) glued into PVC FS boxes and coupled into rigid pvc sch. 40. Is this code compliant? I've been unable to find any reference to it.
Have a great day, Jeff
A
Answer:
Hey Jeff thanks for your question and the kind words. No, only fittings listed for use with liquidtight flexible nonmetallic conduit (LFNC) are allowed to be used as stated in 356.42