Wednesday, June 6, 2018
Question:
Can I run emergency conduit and a normal power conduit into the same j-box
Frank Kanellis
A
Answer:
Hey Frank thanks for your question. Maybe. Emergency system wiring must be kept entirely independent from other wiring as stated in the second sentence of 700.10(B) - unless allowed by (B)(1) through (B)(5). If you meet the conditions such as in (2) or (3) then yes, if not then no.