Thursday, June 21, 2018
Question:
We have the feed for the HVAC disconnects rising through the rubber roofing about a foot away from the HVAC unit and under the disconnect. It is with in the 30 inch working clearance, but does not stop you from safely servicing the disconnect. Is this a code violation?
Dale Stone
A
Answer:
Hey Dale thanks for your question. If the wiring method used to supply the disconnecting means is under the disconnecting means then it is not in the 30 inch minimum width that is required in front of electrical equipment as stated in 110.26(A)(2). If that is not what you are describing send in a comment and we will try provide a better answer.