Monday, May 31, 2021
Question:
Hello,
Does a pool equipment sub panel located remotely from a structure require a grounding electrode system?
Tom Ekstrom
A
Answer:
Hi Tom,
The definition of the word "Structure" has been revised to include the words "other than equipment." Based on the information in the question, a grounding electrode installed for pool equipment would be considered an auxiliary grounding electrode as addressed in Section 250.54.