National Electrical Installation Standards

Standards as High as Your Own

 
?
Wednesday, May 30, 2018

Question:

Hey Charlie, I have a continuous duty motor that I am feeding from a VFD. The VFD is fused at 60 amps and is fed from a 480 volt panel. I used NEC table 430.250 for the FLA and for a 20 HP motor it has a 27 IFLA. My drawing shows a 60 amp breaker (instantaneous trip) feeding the VFD with # 8 AWG THHN. I know you can oversize your breaker for motors, but where in the NEC does it show that #8 is good for a 60 amp breaker. According to 310.15 (B) (16) , #8 is only good for 55 amps.

Thanks for your help, Michael from New Mexico

A

Answer:

Hey Michael from New Mexico thanks for your question. Let's start with your example without an adjustable speed drive to help explain the NEC rules. Conductors must be protected based their ampacities unless different rules in 240.4(A) through ((G) apply as stated in 240.4. Section 240.4(G) allows the use of Table 240.4(G) which includes a reference to Article 430, Parts II to VII.

Conductors supplying a single motor must have an ampacity at least 125 % of the motor full load current (FLC) rating as stated in 430.22(A) based on the Table Values (430.250 as you indicate) which are referenced in 430.6(A)(1).

The motor and motor branch circuit also need overload protection as sated in 430.32 which is generally either 125% or 115 % of the motor nameplate current value based on 430.6(A)(2).

Instantaneous trip circuit breakers are only allowed if adjustable and part of a listed combination motor controller as stated in 430.52(C)(3). Table 430.52 contains the maximum ratings of overcurrent protective devices based on a percentage of the motor FLC.

The overcurrent device, that is used for short circuit and ground fault protection, can be sized higher (oversized) than the conductor ampacity is because overload protection is provided which often "matches" the 125% required for the motor conductors. If the conductors were protected based on their ampacity it is likely the overcurrent protection device would operate when the motor was started due to inrush current.

Using your 20 hp 460 volt motor with the 27 ampere rating from Table 430.250 times 125% from 430.22 gives us a value of 33.75 amperes for minimum conductor ampacity. Without any adjustment or correction factors and assuming 60 degree terminations for the equipment based on 110.14(C) the allowable ampacity of 40 for an 8 AWG copper conductor sufficient. If you actually have an inverse time circuit breaker, used for short circuit and ground fault protection, it can have a rating of 250% of the motors FLC rating as stated in Table 430.52. The 27 ampere value times 250% gives us 67.5 for the maximum circuit breaker rating without using exception No 1 from 430.52(C)(1) so a 60 ampere circuit breaker is acceptable.

For adjustable speed drive systems (could be a VFD) the conductors must have an ampacity of 125% of the drives input current rating as stated in 430.122(A). There are also specific branch circuit short circuit and ground fault protection rules in 430.130 for adjustable speed drive systems.

ABOUT CQD: The Code Question of the Day (CQD) is NECA and ELECTRICAL CONTRACTOR Magazine’s flagship National Electrical Code (NEC®) public forum for the industry, sponsored by EATON. The daily distribution of Q&A generates a lively dialogue and shares relative Code-based practical responses.

SUBMIT YOUR CODE QUESTION: Click here to submit a question to for inclusion in an upcoming edition of the Code Question of the Day, or email codequestion@necanet.org

CHARLIE TROUT: Charles M. Trout, better known as Charlie, was a nationally known NEC® expert and author. He served on several NEC® technical committees and is past chairman of CMP-12. In 2006 Charlie was awarded the prestigious Coggeshall Award for outstanding contributions to the electrical contracting industry, codes and standards development, and technical training. Even though Charlie passed away in October of 2015, his work continues in spirit. NECA continues to maintain this question forum for its many subscribers in memory and recognition of all his significant contributions to making the NEC what it is today.

NECA STANDARDS: NECA publishes the National Electrical Installation Standards™ (NEIS™), a series of ANSI-approved performance and quality standards for electrical construction. NEIS can be purchased in the NECA Store in three formats: a printed or  PDF download of a standard or, as an  annual subscription service.

NECA SAFETY PRODUCTS & PUBLICATIONS: NECA produces electrical safety publications and products for the industry including jobsite safety guides, handbooks and resource kits. View a full listing of available resources and products »

IMPORTANT NOTICE: Unless the question requests a response based on a specific edition, all answers are based on the latest edition of NFPA 70® National Electrical Code®.

This correspondence is not a formal interpretation of the NEC® and any responses expressed to the questions are opinions and do not necessarily represent the official position of NECA, NFPA, the NEC Correlating Committee any Code-making panel or other electrical technical committee. In addition, this correspondence is neither intended, nor should it be relied upon, to provide professional consultation or services. 

UPDATE YOUR SUBSCRIPTION PREFERENCES: Subscribe or Unsubscribe from this list.