?
Friday, May 12, 2017
Question:
Thank you in advance. 300.15(F).
A “go-from” (transition or combination coupling) when being used for a cable to conduit, example; MC to EMT. Would this be considered a pull point that would require the fitting to be accessible? Personally, I do not believe it is a pull point but I have been wrong before Thank you, Jim Dorsey
A
Answer:
Hey Jim thanks for your question and you are welcome, we have all been wrong before. It seems it would be considered a pull point based on the concept and wording in 300.15. The section title has the words "Boxes, Conduit Bodies, or Fittings" and because the transition is not a conductor splice point, outlet point, switch point, junction point, or termination point the only one left is a pull point. Besides, the fitting must be accessible after installation as stated in the last sentence of 300.15(F).