Question:

Hi and Peace to you, well there is always some installation practices that seem to arise. I have my thoughts on what the code says, really like to hear what you say the code states. Can one use a green THWN insulated equipment ground run with URD in a trench (direct buried) (feeder or even branch circuit) or even connected to a concrete encased electrode? What if the outer jacket is removed and only the bare copper wire is now exposed to the direct buried elements? I see 310.10 (F), 250.118&119,300.5 coming into play and maybe the white book. Will look forward to your code answers. Thanks.

Butch Gosselin

A

Answer:

Hey Butch thanks for your question, there are multiple possible answers. Conductors that are directly buried must be identified for that use as stated in 310.10(F). In general wire type equipment grounding conductors can be bare, covered or insulated as stated in 250.118(1). Bare aluminum equipment grounding conductors are not allowed to be in direct contact with masonry or the earth, or be terminated within 18 inches of the earth, as stated in 250.120(B). But that restriction does not apply to copper conductors. Similar rules for aluminum grounding electrode conductors are in 250.64(A). It is very common to use either bare or insulated copper grounding electrode conductors underground where connected to grounding electrodes. Bare copper conductors are also used as grounding electrodes in 250.52(A)(3) and 250.52(A)(4).

Equipment grounding conductors installed underground for agricultural buildings must be insulated as stated in 547.5(F). So, if not at an agricultural application then is seems copper equipment grounding conductors should not be an issue underground whether they are bare, covered or insulated. Make sure the AHJ agrees and there are no local restrictions. An exception to 310.10(F) that allows bare or covered wire type equipment grounding conductors underground would make the rules clearer in the future.

ABOUT CQD: The Code Question of the Day (CQD) is NECA and ELECTRICAL CONTRACTOR Magazine’s flagship National Electrical Code (NEC®) public forum for the industry, sponsored by EATON. The daily distribution of Q&A generates a lively dialogue and shares relative Code-based practical responses.

SUBMIT YOUR CODE QUESTION: Click here to submit a question to for inclusion in an upcoming edition of the Code Question of the Day, or email codequestion@necanet.org

CHARLIE TROUT: Charles M. Trout, better known as Charlie, was a nationally known NEC® expert and author. He served on several NEC® technical committees and is past chairman of CMP-12. In 2006 Charlie was awarded the prestigious Coggeshall Award for outstanding contributions to the electrical contracting industry, codes and standards development, and technical training. Even though Charlie passed away in October of 2015, his work continues in spirit. NECA continues to maintain this question forum for its many subscribers in memory and recognition of all his significant contributions to making the NEC what it is today.

NECA STANDARDS: NECA publishes the National Electrical Installation Standards™ (NEIS™), a series of ANSI-approved performance and quality standards for electrical construction. NEIS can be purchased in the NECA Store in three formats: a printed or  PDF download of a standard or, as an  annual subscription service.

NECA SAFETY PRODUCTS & PUBLICATIONS: NECA produces electrical safety publications and products for the industry including jobsite safety guides, handbooks and resource kits. View a full listing of available resources and products »

IMPORTANT NOTICE: Unless the question requests a response based on a specific edition, all answers are based on the latest edition of NFPA 70® National Electrical Code®.

This correspondence is not a formal interpretation of the NEC® and any responses expressed to the questions are opinions and do not necessarily represent the official position of NECA, NFPA, the NEC Correlating Committee any Code-making panel or other electrical technical committee. In addition, this correspondence is neither intended, nor should it be relied upon, to provide professional consultation or services. 

UPDATE YOUR SUBSCRIPTION PREFERENCES: Subscribe or Unsubscribe from this list.