Friday, December 17, 2021
Question:
Good Morning CQD,
Do fuses that are less than 50 amps have to be readily accessible or just accessible for industrial machinery or equipment?
Jimmy Hinton
A
Answer:
Hello Jimmy.
Thanks for participating. The accessibility requirements for overcurrent protective devices, including fuses are provided in Section 240.24 and 240.30(A). Based on the information in the question, the fuses could be located in the enclosure that is able to be accessed by use of tools as indicated in the Exception to 240.24(A).
Hope this is useful.