Tuesday, December 12, 2017
Question:
Is it ok to put fused and infused conductors threw a 12 " pvc nipple, from a trough to a disconnect?
Michael Dolan
A
Answer:
Hey Michael thanks for you question. If by fused and unfused you mean service conductors that usually do not have overcurrent protection where they receive their supply, then no it is not allowed as stated in 230.7. Other conductors such as tap conductors are allowed in the same raceway with those having overcurrent protection at the supply.