Question:
Can you feed a receptacle on the outside of the garage wall off the load side of gfci that is in the garage?
Boyd Lamb
A
Answer:
Hey Boyd thanks for your question. Yes. At least one 20 ampere branch circuit must be installed to supply the receptacle outlets in attached and detached garages at dwelling units as stated in 210.11(C)(4). The exception allows readily accessible outdoor receptacle outlets to be supplied from that same branch circuit.