Question:
Thanks for this Code Forum. In regards to Friday 8/14 answer to breaker tie, if the circuits are 20A, the receptacle will need to be 20A rated when splitting a 15A receptacle now makes a single outlet on the branch circuit see NEC 210.21(B)(1).
Robert Nakamichi
A
Answer:
Hello Robert,
Thanks for the comment and the question. You are correct. If two individual branch circuits each supply one of the two receptacles of a duplex receptacle and the tabs are broken, making them two separate circuits and separate receptacles, then they would need to be 20-ampere rated. A duplex 15-ampere receptacle would not meet the NEC requirements in this case.