Question:
Can service conductors and load conductors be inside the same pull box or is that an NEC code violation?
Aaron McClanahan
A
Answer:
Hey Aaron thanks for your question. It is allowed to have service conductors and other types of conductors in the same box or enclosure. Other types of conductors are not allowed in the same raceway with service conductors as stated in 230.7. But boxes are not raceways as the term Raceway is defined in Article 100.