Thursday, October 31, 2019
Question:
About hospital grade receptacles. I do not find the requirement in 517.18(B) that it must be identified with a ‘green dot’. May be in other Section?
Carlos Gonzalez
A
Answer:
Hey Carlos thanks for your question. As you mention 517.18(B) requires patient bed location receptacles to be listed "hospital grade" and to be so identified.
The information for how the Hospital Receptacle is to be identified is in the Guide Information for the product category. The green dot and additional marking are required by that. This link will give you the information included for receptacles Category (CCN) RTRT
If you have not already registered (for free) to use the UL Product iQ site (See CQD for 10/29/2019) click here »