National Electrical Installation Standards

Standards as High as Your Own

 
?
Monday, October 22, 2018

Question:

I'm an electrician for the government and I been fighting this issue with our building manager and a project manager about multi branch circuits. They have been installed and are used to supply power to nonlinear loads to lighting and also receptacles which feed medical equipment. They have allowed electrical contractors to use 3 ungrounded conductors and one shared neutral from a 4 wire 3 Phase systems using 3 pole type breakers sharing one neutral. Violation of article 410.130(G)(2) none of the neutral conductors have a disconnection means. This was back in 2011, but they still continue to allow this practice, the electrical contractor has stipulated that the installation are in no way in violations to the NEC. So even though 225.33(B), 230.71(B) and 240.15(B), permit two or three single-pole switches or breakers on the multiwire branch circuits that are capable of individual operation—one pole for each ungrounded conductor and one multipole disconnect—provided these devices are equipped with identified handle ties or a master handle to disconnect all ungrounded conductors. Does that mean that’s its ok to use a three pole breakers, with ties, marked in accordance to the code to be use to feed lighting and receptacle circuits that use 3 ungrounded conductors and a share a neutral. Most of the buildings are medical in natural, 3 are dental clinics that do provide surgical care and main building was a hospital but was reduced to clinical services now. Thanks any help to explain if this practice of using a multi branch circuit is still in accordance with new 2017 NEC standards and was this practice allowed back in 2011

Adolfo Munoz

A

Answer:

Hey Adolfo thanks for your question and your concern for safety. In the 2002 NEC multiwire branch circuits (as they are defined in Article 100) supplying more than one device or equipment on the same yoke had to have a means to simultaneously disconnect all ungrounded conductors of the circuit at the panelboard for dwelling units as stated in 210.4(B). That section was changed in the 2005 NEC to remove the dwelling only applicability and the simultaneous disconnecting means was to be located where the branch circuit originated. For the 2008 NEC that section was again changed to remove the words " more than one device or equipment on the same yoke" so all multiwire branch circuits require a means to simultaneously disconnect all ungrounded conductors.

Section 410.73(G) was added in the 2005 NEC to require indoor fluorescent luminaires ballasts to have a means to simultaneously disconnect all conductors of the ballast including grounded conductors with an effective date of January 1, 2008. That section was changed and relocated to 410.130(G) as part of the reorganization of Article 410 for the 2008 NEC. There are products readily available for this purpose,

Articles 225 and 230 do not apply to your example because they are for branch circuits and feeders or services - that supply buildings or structures.

Multi-wire branch circuits (shared neutral) are allowed if all the rules are followed. You will need to find out when (or if being you are government) the 2008 NEC was adopted in your area. You don't mention voltages but 240.15(B) applies to multiwire branch circuits and 410.130(G) applies to specific types of luminaires. Notice that disconnecting means must be installed if ballasts are replaced in existing installations.

Finally branch circuits supplying receptacles at patient bed locations in both general care and critical care cannot be supplied by multiwire branch circuits as stated in 517.18(A) and 517.19(A).

ABOUT CQD: The Code Question of the Day (CQD) is NECA and ELECTRICAL CONTRACTOR Magazine’s flagship National Electrical Code (NEC®) public forum for the industry, sponsored by EATON. The daily distribution of Q&A generates a lively dialogue and shares relative Code-based practical responses.

SUBMIT YOUR CODE QUESTION: Click here to submit a question to for inclusion in an upcoming edition of the Code Question of the Day, or email codequestion@necanet.org

CHARLIE TROUT: Charles M. Trout, better known as Charlie, was a nationally known NEC® expert and author. He served on several NEC® technical committees and is past chairman of CMP-12. In 2006 Charlie was awarded the prestigious Coggeshall Award for outstanding contributions to the electrical contracting industry, codes and standards development, and technical training. Even though Charlie passed away in October of 2015, his work continues in spirit. NECA continues to maintain this question forum for its many subscribers in memory and recognition of all his significant contributions to making the NEC what it is today.

NECA STANDARDS: NECA publishes the National Electrical Installation Standards™ (NEIS™), a series of ANSI-approved performance and quality standards for electrical construction. NEIS can be purchased in the NECA Store in three formats: a printed or  PDF download of a standard or, as an  annual subscription service.

NECA SAFETY PRODUCTS & PUBLICATIONS: NECA produces electrical safety publications and products for the industry including jobsite safety guides, handbooks and resource kits. View a full listing of available resources and products »

IMPORTANT NOTICE: Unless the question requests a response based on a specific edition, all answers are based on the latest edition of NFPA 70® National Electrical Code®.

This correspondence is not a formal interpretation of the NEC® and any responses expressed to the questions are opinions and do not necessarily represent the official position of NECA, NFPA, the NEC Correlating Committee any Code-making panel or other electrical technical committee. In addition, this correspondence is neither intended, nor should it be relied upon, to provide professional consultation or services. 

UPDATE YOUR SUBSCRIPTION PREFERENCES: Subscribe or Unsubscribe from this list.