Tuesday, February 14, 2023
Question:
Hello Mr. Trout, I am working in an existing 6 story building, and I need to bring a feeder from the basement to the 4
th floor to provide additional power to the new 4
th floor tenant space. There is a stairway that goes all the way from the basement to the roof.
A
Answer:
Hello Tim, the stairwell is most likely a fire-rated egress enclosure stairwell. Section 300.25 limits electrical wiring serving equipment in the stairwell enclosure and permitted by the AHJ. The a general feeder as described in the question is not serving the stairwell enclosure, as such it would not be permitted.